【DO!BOOK・ページリンク】 7-p1379-1411-hec_en 7 / 34 10秒後にBOOKのページに移動します |
|
2. How much is the temperature in degrees centigrade for the circulating fluid? Temperature range which can be set with the Thermo-con: 10 to 60°C If a lower temperature (down to .20°C) or higher temperature (up to 90°C) than this range is necessary, select the Thermo-chiller HRZ series. 1. What radiation method will be used? Without a cooling tower ・・・・・・・・・・ Air-cooled HEC-A series With a cooling tower ・・・・・・・・・・ Water-cooled HEC-W series 3. What kind of the circulating fluids will be used? Allows a safety factor of 20% over the capacity that is actually required, taking into account the changes in the operating conditions. If a larger capacity than this Thermo-con is necessary, select the Thermo-cooler HRG series or Thermo-chiller HRZ series. 4. How much cooling capacity required? Guide to Model Selection Cooling capacity = Considering a safety factor of 20%, 400 x 1.2 = 480 W Heat generation amount: 400 W Example 1 When the heat generation amount in the customer’s machine is known. Circulating fluids that can be used in the Thermo-con Clear water FluorinertTM FC-3238 GALDENR HT135 Model 20% ethylene glycol HEC001-W, HEC003-W HEC006-W, HEC012-W HEC002-A, HEC006-A : Usable : Unusable When to Use Air-cooled and Water-cooled Thermo-con |